All Resources

Overview

author

Quentin Baker
Dan Benac
Douglas Olson

published on

March 2011

A natural gas fired industrial oven exploded during an attempted restart a few hours after a cold start. The explosion was caused by accumulation of natural gas during the hours preceding the restart. The oven had a fully-automated control system, and the start, shutdown, and restart were controlled by process controls and a flame safeguard system. A malfunction of the flame detector allowed the automated controls to complete the start sequence and establish normal operating status without a flame present in the burner. The UV flame sensor gave a false positive signal, which allowed unburned natural gas to enter the oven. The investigation explored the cause of the incident and the failure modes of the flame detector.

Fill out the form to request access.

Copyrighted Resource Form
Name
Name
Marketing Emails Consent

Get to know the authors.

Meet the experts who brought this paper to life.

View all team members

quentin baker, PE, CFEI, CFII

dan benac, PE, CFEI, ASM Fellow

douglas olson