All Resources

Overview

author

Peter Diakow
Kelly Thomas
Phil Parsons

published on

October 2016

This paper presents results from a test program carried out to determine the peak deflagration pressure achieved within a congested enclosure vented through one wall of the enclosure. The industry standard in the United States for predicting the peak pressure developed in a vented deflagration is the National Fire Protection Association’s Standard on Explosion Protection by Deflagration Venting (NFPA 68). The NFPA Explosion Protection Committee has compiled a database of published and unpublished explosion venting test data. This data was summarized in a 2008 report (Zalosh) that served as the foundation of the development for the vented deflagration correlations in the latest (2013) edition of NFPA 68. In this latest edition, NFPA 68 (2013), the vent area correlation accounts for varying degrees of congestion if the ratio of the obstacle surface area (Aobs) to that of the enclosure internal surface area (As) is greater than 0.4 (i.e., Ar ¼ Aobs/As > 0.4). Congestion is accounted for within the correlation at all values of Ar, however when Ar is < 0.4, variations in the level of congestion are not accounted for. The tests described in this paper were performed using an obstacle array with an Ar ratio of less than 0.4.